Should a data centre BMS or DCIM be powered by the same system it is monitoring? Most data centre BMS systems are powered by one of the UPS sets used for the ICT equipment so they are effectively powered by what they are monitoring.
TIA-942 Revision B, 2017 Telecommunications Infrastructure Standard for Data Centers, states “Security, Data Gathering Panels (Field Panels) UPS Capacity, Rating 3: Building UPS or local battery backup (8 hour min).”
We propose that the best design solution is to always have a separate UPS with an 8-hour battery for all BMS/DCIM monitoring and control systems and also security and fire detection systems. As far as possible communications links to the outside world should also be relayed through equipment separate from the data centre’s normal communications systems.
A Rating 4 system, where power and cooling systems maybe duplicated, should have a separate BMS/DCIM capability each with its own UPS-backed power supply. A Rating 3 system with one BMS/DCIM should ideally have two UPS paths feeding it.
BMS/DCIM systems that are monitoring-only are inherently fail-safe as they have no ability to change anything, however a system that can be used to make operational changes or settings must be viewed and used with caution as it can become a single point of failure if it decides to go haywire and send erroneous command signals to vital power or cooling equipment.
The recommendations above are appropriate for larger data centres. When we design small data centres we always have a completely separate rack dedicated to the DCIM controller, the door access system, the CCTV controller and recorder and anything else of a monitoring/security nature. In the bottom of the rack we put in a dedicated UPS with the largest battery that will fit. The UPS itself has a manual bypass that can be switched to raw mains or another UPS output to maintain the philosophy of concurrent maintenance for the DCIM and its UPS.