As demand for faster data transmission in AI-driven data centres grows exponentially,
cabling designs must prioritise higher density, scalability and operational efficiency. When it
comes to selecting a cabling configuration in these environments, which is most effective –
point to point or structured cabling ?
We have always been proponents of organised structured cabling installations in data
centres after seeing so many patchcord spaghetti horror shows in computer rooms. We
would point customers toward standards such as TIA942 Telecommunications Infrastructure
Standard for Data Centers and EN50600-2-4 Data centre facilities and infrastructures – Part
2- 4: Telecommunications cabling infrastructure. Cabling architecture is almost exclusively
based on Ethernet (with some Fiber Channel) and Cat6/6A copper cables and OM3/4 fibre.
The arrival of Artificial Intelligence and high density computing has changed that narrow view
and somebody looking to get into the world of products like the NVIDIA DGX SuperPOD and
processors like the NVIDIA DGX GB300 will have to start looking at some form of Direct
Attach Cabling (DAC) just to make it work. A single DGX GB300 unit specification reads 72 x
OSFP single-port with 800Gb/s InfiniBand and 18x dual-port with 200Gb/s InfiniBand and
Ethernet….. and there could be hundreds of these.
This is now recognised in the 2024 edition of TIA942-C;
The use of direct attach cabling as an alternative to structured cabling should be
limited to specific use cases. Direct attach cabling between rows is not recommended.
Any direct attach cabling should be routed in cable management or accessible
pathways, and not interfere with fixed cabling. When direct attach cables are no longer
used, the cables shall be removed.Cable lengths for direct attach cabling between equipment in the EDA should be no
greater than 7 m (23 ft) and should be between equipment in immediately adjacent
(i.e., not multiple) racks or cabinets in the same row.Direct attach cabling within distributors (MDs, IDs, HDs) and entrance spaces should
be constrained within the distributor or entrance space and within a contiguous row.
So we can conclude that for ‘regular’ data centres an overlay structured cabling system is a
must but for high density superpod ‘AI’ type installations direct attached cabling is inevitable
and with copper and fibre InfiniBand looking like the favoured attachment protocol.